Features of the Safer Distribution Board
Change a circuit breaker "Live" with "Dead" Tee Offs for the ultimate in human protection and in safe working practices.
Work on a "Live" Board without coming into contact with Live Phases.
Insulated/shrouded phase busbars, circuit breakers & neutral link
Main Switch
3 or 4 Pole 160amp or 250amp Main Switch/Isolator.
Top or Bottom Connected Boards.
Terminal shields provided with main switch Line & Load sides.
Chassis
Isobar type TNA chassis.
250amp current carrying capacity of the busbar.
100amp current carrying capacity of the outgoing tee-offs.
16KA for 200mSec withstand rating.
25KA conditional withstand rating.
Unique chassis slider switch permits un-used poles to be electrically isolated resulting in enhanced protection against direct contact with live parts during testing, commissioning and retrofit applications.
Earth & Neutral Links
165A earth & neutral bars with two screw Ø5mm tunnels for outgoing cables up to 16mm2 & 2 x M8 hex head screws for incoming cables.
Earth & neutral bars comply with clause 2.9.3.1 of AS/NZS 3000:2000.
Optional PVC Covered Neutral Link for greater protection.
Distribution Board Features
Board sizes from 24 poles to 96 poles.
100% Population of Schneider C60N 6KA Circuit breakers.
Terminal shrouds on all load connections of Circuit Breakers.
Form 4ah as per AS/NZS 3439.1:2002 with shrouding.
Optional Traffolyte labelled.
Pole fillers for auxiliary equipment openings.
Circuit schedule card with transparent plastic protector.
1.6mm sheet steel box, door and escutcheon.
Door on Pintal Hinges.
Removable gland plates - top & bottom.
Flush Locks - including 2 keys per lock.
Chrome D Handles on 36 pole boards and higher.
All enclosures are 580mm wide and 235mm deep.
Transformer Grey (Dulux 32186) powercoated enclosure with white esc.
Orange Coloured Boards - Can be ordered on request.
Weatherproof Boards - Can be ordered on request.
All Distribution Board widths are 580mm
Main Switch
Rating |
MCB Pole capacity
18MM |
Enclosure
Height |
| 160/250amp |
24 pole |
750mm |
|
160/250amp |
36 pole |
1000mm |
|
160/250amp |
48 pole |
1000mm |
|
160/250amp |
54 pole |
1200mm |
|
160/250amp |
72 pole |
1200mm |
|
160/250amp |
84 pole |
1500mm |
|
160/250amp |
96 pole |
1500mm |